Electronic frequency multi-frequency generators are not ordinary tools for routine maintenance, but mandatory diagnostic equipment used at critical junctures such as equipment manufacturing, new installation and commissioning (handover testing), and post-overhaul, to perform "deep health checks" on core power equipment (PTs, transformers, GIS, cables).

In short: they are specialized "CT scanners," ensuring the "smooth flow" (healthy insulation) and "sensitive nerves" (precise signal transmission) of transformers, instrument transformers, and other equipment, forming a crucial link in building a robust smart grid security defense.berita perusahaan terbaru tentang Why are the Electronic frequency multi-frequency generators so important?  0

Why are they so important?

Their importance lies in their irreplaceable technical means to ensure the safe and reliable operation of the power grid.

A keen eye helps you discover hidden insulation defects.
  • Problem: Many serious insulation defects (such as inter-turn short circuits, winding deformation, and internal particles in GIS) cannot be exposed in conventional power frequency withstand voltage tests.
  • Solution: Multi-frequency testing, by altering the electric field frequency distribution, can accurately excite and detect these "potential" defects, preventing equipment from being put into use with defects present.
Core Technology for Preventing Core Magnetic Saturation
  • Principle: According to the formula V = 4.44fNBA, voltage (V) is proportional to frequency (f) and magnetic flux density (B). The only way to increase voltage V without causing core burnout due to magnetic flux density B saturation is to simultaneously increase frequency f.
  • Importance: This is the only safe and effective method for rigorous insulation testing of electromagnetic PTs and transformers.
Key Enablement for Field Testing of Large Equipment
  • Problem: Testing capacitive equipment (such as GIS and long cables) at power frequency requires enormous power capacity (KVA), making the equipment bulky and impassable in the field.
  • Solution: Required power capacity S x f. Theoretically, increasing the frequency from 50Hz to 150Hz can reduce the power capacity requirement by 2/3, allowing for field testing with relatively lightweight equipment.
Compliance with mandatory international standards

Standard basis: The International Electrotechnical Commission (IEC) and national standards (GB) clearly stipulate that the insulation testing of the above-mentioned equipment requires induced withstand voltage testing or frequency conversion withstand voltage testing.

  1. IEC 60076-3 (Power Transformers)
  2. IEC 61869-1 (Instrument Transformers)
  3. GB 50150-2016 (Acceptance Testing Standards for Electrical Equipment in Electrical Installations)